A response factor-based method for the rapid in-situ determination of wall’s thermal resistance in existing buildings

Research output: Contribution to journalArticleScientificpeer-review

53 Citations (Scopus)

Abstract

The in-situ estimation of the thermal resistance (Rc-value) of walls in buildings is of major significance to determine their energy performance. The exact construction of walls is generally unknown, especially in older buildings, making the estimation of the Rc-value inaccurate. In-situ measurement is generally not being performed because, for the current standard method (ISO 9869), generally a measurement period of more than ten days is required. In the present paper, a new transient in-situ measurement method (Excitation Pulse Method, EPM) based on the theory of response factors is derived, applied experimentally on three walls, showing that it is possible to measure the Rc-value within less than 2 h. The results are compared to the ones obtained by ISO 9869 method, showing a good agreement. Additionnally, EPM measurement technique can provide the average Volumetric Heat Capacity and thermal conductivity. It is also shown that the ISO 9869 method can be easily improved by using an additional heat flux meter. EPM is believed to make a significant contribution to the quick and accurate estimation of the thermal resistance in unknown constructions and therefore to the accuracy of the prediction of energy consumption in buildings.
Original languageEnglish
Pages (from-to)51-61
JournalEnergy and Buildings
Volume119
DOIs
Publication statusPublished - 2016

Keywords

  • In-situ measurement
  • Thermal resistance Rc-value
  • Thermal transmittance U-value
  • Response factors
  • Transient method
  • Energy labeling

Fingerprint

Dive into the research topics of 'A response factor-based method for the rapid in-situ determination of wall’s thermal resistance in existing buildings'. Together they form a unique fingerprint.

Cite this