Abstract This letter deals with the hybrid modeling of transformers and the determination of interturn voltage distribution in transformers with layer-type windings. The hybrid model uses a combination of a multiconductor transmission-line model and a single transmission-line model. The good agreement between computed and measured voltage waveforms shows that this model can be used for the computation of interturn voltages with full success. Analysis is performed by making use of a step function with 100-ns rise time.
Original languageUndefined/Unknown
Pages (from-to)1742-1744
Number of pages3
JournalIEEE Transactions on Power Delivery
Volume24
Issue number3
DOIs
Publication statusPublished - 2009