Abstract
This article describes the circulating current phenomenon that takes place in bipolar, meshed DC distribution grids. A difference in resistance between the conductor changes the distribution of the current on the conductors. This provokes a net current to flow, which is in turn measured by the residual current protection scheme, used to detect and isolate ground faults in the system, even though there is no fault in the system. Due to the circulating tendency of this net current, the operation of the protection scheme can be prevented in such a case by the addition of a clever communication system.